Level Transmitters
Magne-Trac with the FMP 40 Guided Wave Radar
SMART TRANSMITTER FOR:
- Level Measurement in Bulk Solids and Liquids
- Interface Measurement in Liquids
BENEFITS:
Probes are available with threaded process connections
from ¾" and flanges from DN40 / 1½.
- Rope probes, above all for measurement in bulk solids, measuring range up to 35 m.
- Rod probes, above all for liquids
- Coax probes, for liquids
- Simple, menu-guided onsite operation with four-line plain text display.
- Onsite envelope curve on the display for easy diagnosis.
- Easy remote operation, diagnosis and measuring point documentation with the free operating program supplied.
- Optional remote display and operation.
- With coax probes the measurement is independent of internals in the tank and of the installation in the nozzle.
- Probe rod and probe rope can be replaced/shortened.
- Approvals: ATEX, FM, CSA, TIIS, NEPSI, IECEx.

Click HERE to download Bridle Specification Guide |
  |
Level measurement:
Continuous level measurement of powdery to granular bulk solids e.g. plastic granulate and liquids.
- Measurement independent of density or bulk weight, conductivity, dielectric constant, temperature and dust e.g. during pneumatic filling.
- Measurement is also possible in the event of foam or if the surface is very turbulent.
- The HART with 4 to 20 mA analog, PROFIBUS PA and FOUNDATION Fieldbus protocols are available for system integration.
- Application in safety related systems (overspill protection) with requirements for functional safety up to SIL 2 in accordance with IEC 61508/IEC 61511-1.
- WHG approval
|
Interface measurement
- Continuous measurement of interfaces between two liquids with very different dielectric constants, such as in the case of oil and water for example.
- Measurement independent of density, conductivity and temperature
- Electronics version for the simultaneous measurement of the level of interfaces and the total level in liquids. The HART with 4 to 20 mA analog protocol is available for system integration.
- Special version for the measurement of the level of interfaces at a constant total level. The PROFIBUS PA and FOUNDATION Fieldbus protocols are available for system integration
|
Measuring range |
- up to 4 m / 13 ft
(Rod probe, Coax probe)
up to 35m / 114 ft
(Rope probe)
|
Dielectric constant |
- 1.6 (Rod probe, Rope probe)
- 1.4 (Coax probe)
|
Temperature |
- -40...150 °C / -40...302 °F
|
Probes: |
- Rod probe
- Coax probe
- Rope probe
|
Pressure |
|
|
|