Measurement Principle | Guided time-of-flight via time domain reflectometry |
---|
Input
Measurement Variable | Level, determined by the time-of-flight of a guided radar pulse from transmitter to product surface and back |
---|
Zero and Span | 6 inches to 75 feet ( 15 to 2286 cm) |
---|
User Interface
Keypad | 3-button menu-driven data entry and system security |
---|
Indication | 2-line x 8-character display |
---|
Digital Communication | HART, Fieldbus |
---|
Minimum Operating Voltage | 9 VDC |
---|
Quiescent Current Draw | 15 mA |
---|
DEV Revision | 0X01 |
---|
Function Blocks | Al_1, Al_2, Al_3, Al_4 |
---|
Damping | Adjustable 0-10 seconds |
---|
Power
(Measured at instrument terminals)
General Purpose / Explosion Proof | 9 to 32 VDC ( 15 mA maximum current draw) |
---|
IS/FISCO/FNICO | 9 to 32 VDC ( 15 mA maximum current draw) |
---|
Housing
Material | Aluminum A356T6 (<0.20% copper), optional 316 SST |
---|
Cable Entry | ¾” NPT and M20 |
---|
Environment
Operating Temperature | -196 to +842°F (-320 to +450°C) Model Dependent |
---|
Pressure | Vacuum -14.5 to 5,800psi (Vacuum -1 to +400bar) Model Dependent |
---|
Display Function Operating Temperature | -5 to +160°F (-20 to +70°C) |
---|
Storage Temperature | -50 to +175°F (-40 to +80°C) |
---|
Humidity | 0-99%, non-condensing |
---|
Electromagnetic Compatibility | Meets CE Requirements: EN 50081-2, EN 50082-2 |
---|
Shock Class | ANSI/ISA-S71.03 Class SA1 |
---|
Vibration Class | ANSI/ISA0S71.03 Class VC2 |
---|
Reference Conditions | Reflection from water +70°F (+20°C) with 72” coaxial probe (CFD threshold) |
---|
Linearity | Coaxial/Twin Rod Probes: | <0.1% of probe length or 0.1 inch (whichever is greater) |
---|
| Single Rod Probes: | <0.3% of probe length or 0.3 inch (whichever is greater) |
Measured Error | Coaxial/Twin Rod Probes: | ±0.1% of probe length or 0.1 inch (whichever is greater) |
---|
| Single Rod Probes: | ±0.5% of probe length or 0.5 inch (whichever is greater) |
Resolution | ±0.1 inch |
---|
Repeatability | <0.1 Inch |
---|
Hysteresis | <0.1 Inch |
---|
Response Time | <1 second |
---|
Warm-up Time | <5 seconds |
---|
Operating Temp. Range | -40° to +175°F (-40° to +80°C) |
---|
LCD Temp. Range | -5° to +160°F (-20° to +70°C) |
---|
Ambient Temp. Effect | Approximately +0.02% of probe length/ °C |
---|
Process Dielectric Effect | <0.3 inch within select range |
---|
Humidity | 0-99%, non-condensing |
---|
Electromagnetic Compatibility | Meets CE Requirements (EN-61000-6-2/2001, 61000-6-4/2001) |
---|